The number and location of destratifiers is determined individually for each installation according to the following rules:
- destratifiers are placed at 2/3 of the height of the object,
- the recommended maximum installation height must not be exceeded,
- the volume of destratification should be approximately 1,6 - 2 times the volume of the building,
- the type of destratifier is determined according to the installation height and the required air flow.
See this example: a building with dimensions of 85 m x 16 m x 8,5 m, the volume of the building is 11,560 m³:
- the volume of destratified air is twice the volume of the building (23,120 m³/h),
- we choose a destratifier according to the suspension height (7m) and air volume (23,120 m³/h),
- the number of destratifiers according to air volume and suspension height is 2 pieces, type A10.
Destratifier technical details:
Type | Air flow [m3/h] | Noise level [dB] | Number of fans [pcs] | Electric power [W] | Instalation height, max. [m] | Weight [kg] |
A4 | 3600 | 41 | 1 | 160 | 4 | 18 |
A6 | 5500 | 48 | 1 | 430 | 6 | 21 |
A10 | 9400 | 51 | 2 | 410 | 10 | 36 |
Destratifier dimensions
Type | A | B | C |
A4 | 600 | 650 | 400 |
A6 | 600 | 650 | 400 |
A10 | 650 | 1200 | 400 |